Issue |
EPJ Web of Conferences
Volume 25, 2012
EFM11 – Experimental Fluid Mechanics 2011
|
|
---|---|---|
Article Number | 01031 | |
Number of page(s) | 5 | |
Section | Experimental Fluid Mechanics 2011 | |
DOI | https://doi.org/10.1051/epjconf/20122501031 | |
Published online | 16 April 2012 |
https://doi.org/10.1051/epjconf/20122501031
Fluid flow in panel radiator under various conditions - thermographic visualisation
FS ČVUT v Praze, Ústav techniky prostředí, Technická 4,
16600 Praha 6
L.Jancik@fs.cvut.cz
Thermographic investigation of a heating panel radiator under various conditions, especially with various heating water volume flow rate is described in this article. For a radiator type 10-500x1000 TBOE and for two levels of inlet water temperature (75 and 55 °C) a set of thermal images of surface temperature patterns for various values of heating water volume flow rate was taken. The initial value of flow rate was derived from nominal heating output and recalculated to real conditions. An increase of volume flow rate higher than 15 % over the nominal recalculated value is for the studied cases easily detectable on the resulting thermal images.
© Owned by the authors, published by EDP Sciences, 2012
Current usage metrics show cumulative count of Article Views (full-text article views including HTML views, PDF and ePub downloads, according to the available data) and Abstracts Views on Vision4Press platform.
Data correspond to usage on the plateform after 2015. The current usage metrics is available 48-96 hours after online publication and is updated daily on week days.
Initial download of the metrics may take a while.