Check valve slam analysis in pumping station
Brno University of Technology, Faculty of Mechanical Engineering, Energy Institute, Victor Kaplan Department of Fluid Engineering, Technická 2, 616 69, Brno, Czech Republic
a e-mail: himr@fme.vutbr.cz
Published online: 28 March 2016
Pumping station supplies water for technological process. The check valve in the station was replaced with a new one. The regular test of black out discovered the high pressure pulsations accompanied with noticeable pipeline movement of discharge pipe. It was caused by late check valve closing, probably, when the back flow reached the highest possible velocity. This statement was supported with analysis of results of pressure measurement near the check valve and with a numerical simulation of the flow in the pipeline system.
© Owned by the authors, published by EDP Sciences, 2016
This is an Open Access article distributed under the terms of the Creative Commons Attribution License 4.0, which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited.
Current usage metrics show cumulative count of Article Views (full-text article views including HTML views, PDF and ePub downloads, according to the available data) and Abstracts Views on Vision4Press platform.
Data correspond to usage on the plateform after 2015. The current usage metrics is available 48-96 hours after online publication and is updated daily on week days.
Initial download of the metrics may take a while.